Tripp Lite SU1500RTXL2UA Fiche technique

Naviguer en ligne ou télécharger Fiche technique pour Alimentations sans interruption (UPS) Tripp Lite SU1500RTXL2UA. Tripp Lite SmartOnline 100-120V 1.5kVA 1.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower,USB, DB9 Serial Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 6
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
SmartOnline 100-120V 1.5kVA 1.2kW On-Line
Double-Conversion UPS, Extended Run, SNMP,
Webcard, 2U Rack/Tower,USB, DB9 Serial
MODEL NUMBER: SU1500RTXL2UA
Description
Requiring only two rack spaces (2U) in a standard rack enclosure, Tripp Lite's SU1500RTXL2Ua SmartOnline
UPS System protects connected equipment against data loss, downtime and equipment damage due to power
outages, voltage fluctuations and transient surges. Featuring true on-line operation with pure sine wave output
and zero transfer time to battery, it provides the highest level of power protection for mission-critical equipment.
Internal batteries support connected equipment during blackouts, and runtime is expandable with optional
external battery packs. The SU1500RTXL2Ua has six outlets arranged in two individually controllable load banks
that can be used to reboot select equipment on demand or maximize battery runtime for mission-critical
equipment. USB and DB9 communication ports support messaging of detailed UPS operational parameters and
line power status. Included PowerAlert UPS monitoring and unattended shutdown software provides
management support for an unlimited number of network UPS systems.
Features
SmartOnline high-performance UPS system is ideal for critical voice, data, medical and industrial network
applications
True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 100/110/120V (user selectable) under all usage
conditions
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types
Corrects line voltage conditions as low as 65V and as high as 150V back to selectable 100/110/120V (+/-2%) values
Standard internal battery set offers 14 min. runtime at half load (600W) and 5 min. at full load (1200W)
Extended runtime available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible)
external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Highlights
1500VA / 1.5kVA / 1200 watt
on-line double-conversion 2U
rack/tower UPS
100/110/120V +/-2% output at
50/60Hz, high efficiency
economy mode option
Expandable runtime, Hot-swap
batteries; 19 in / 48.3cm installed
depth
USB, RS232 & EPO ports;
support for SNMP/WEB card
options
Front panel status LEDs with
detailed load and battery metering
2 independently switchable
output load banks
NEMA 5-15P input; 5-15R outlets
Applications
Distributed Server Rooms
Network Closets
Small Business Networks
Voice over IP (VoIP) Phone
Systems
Package Includes
SU1500RTXL2Ua UPS System
PowerAlert Software CD
1 x 6-ft. USB Cable
1 x 6-ft. DB9 Cable
4-Post Rackmounting Hardware
Owner's Manual
1 / 6
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - MODEL NUMBER: SU1500RTXL2UA

SmartOnline 100-120V 1.5kVA 1.2kW On-LineDouble-Conversion UPS, Extended Run, SNMP,Webcard, 2U Rack/Tower,USB, DB9 SerialMODEL NUMBER: SU1500RTXL2UA

Page 2 - Specifications

Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 in. Ships with all mounting accessorie

Page 3

Output Voltage Regulation(Economy Line Mode)+/- 10%Output Voltage Regulation (BatteryMode)+/- 2%Output Receptacles (6) 5-15RUPS Output Receptacles (Su

Page 4

Overvoltage Correction 2% output voltage regulation during overvoltages to 150Undervoltage Correction 2% output voltage regulation during undervoltage

Page 5

Included Battery Pack Dimensions(hwd / in.)OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%l

Page 6

High Voltage Transfer to BatteryPower (Setpoint)150SPECIAL FEATURESCold Start (Startup in Battery ModeDuring a Power Failure)Cold-start operation supp

Commentaires sur ces manuels